Standards, Codes & Basic Electronics
Industry standards, electrical codes, basic electronics and circuit fundamentals, NEC articles in exam order, wire types and fire ratings, grounding rules, resistor color codes, and voltage-drop calculations — the foundation every NYS alarm installer must know cold.
Important acronyms & key terms
Key numbers, codes & rules
01Part 1 — Standards & Organizations
Several bodies create the rules that govern alarm installation. Understanding who does what is a guaranteed exam topic.
Standards → Codes → Law → Enforcement
The Key Organizations
- ANSI (American National Standards Institute) — writes the guides used to develop standards and codes.
- UL (Underwriters Laboratories) — tests and lists equipment; judges installations against set standards.
- UL also lists companies for specific types of installations, in addition to testing/listing equipment and judging installations against set standards.
- NFPA (National Fire Protection Association) — publishes the national fire and electrical standards (NEC, NFPA 72, 101, 170).
- FM (Factory Mutual) — also tests equipment but less widely used than NFPA/UL; does not always agree with NFPA.
- AHJ (Authority Having Jurisdiction) — interprets rules, enforces the code, approves equipment in your local area.
- MRLS — municipalities have the right to enact a "More Restrictive Local Standard" stricter than the state standard.
- Code changes happen through committee/board review, or by petition from individuals, industry groups (lobbying), or outside parties.
- In NY, the DOS Division of Code Enforcement and Administration trains Code Enforcement Officials (CEOs) and maintains the Energy Conservation Construction Code; codes are reviewed on a 3-year ICC cycle (e.g., the 2010 CO-detector requirement).
- RCNYS: in this "home rule" state, the Residential Code of NYS is an alternate compliance path for residential electrical work.
- Codes state minimums — a local code cannot override a higher authority (Federal > State > County > Town > AHJ).
NFPA Documents You Must Memorize
| Document | Covers |
|---|---|
| NFPA 70 | National Electrical Code (NEC) |
| NFPA 72 | Fire Alarm Systems |
| NFPA 101 | Life Safety Code |
| NFPA 170 | Fire Alarm Symbols |
02Part 2 — NEC Articles You Must Know
The National Electrical Code (NEC / NFPA 70) governs all electrical and low-voltage wiring in the United States. First published in 1897, updated every three years, adopted in all 50 states. Know these eight articles in this exact order.
NEC Articles — Exam Order
Blue = General Electrical · Green = Installation · Red = Safety · Purple/Orange = Alarm-Specific
Article 90 — Purpose of the NEC
Article 90 defines WHY the NEC exists and establishes the authority framework. It is tested on almost every exam.
- Purpose (90-1): The NEC exists for the practical safeguarding of persons and property from hazards arising from the use of electricity.
- Adequacy: Contains provisions considered necessary for safety — compliance does NOT guarantee an efficient, convenient, or adequate installation.
- NOT a design spec: The Code is NOT intended as a design specification and NOT an instruction manual for untrained persons.
- Enforcement (90-4): Intended for mandatory application by governmental bodies. The AHJ has authority for interpretations, approvals, and granting special permissions.
- Formal Interpretations (90-5): Formal Interpretation Procedures promote uniformity in applying the NEC.
Article 110 — Requirements for Electrical Installations
Article 110 establishes how electrical work must be executed — quality, approval, and workmanship standards.
- 110-12 Mechanical Execution: All electrical equipment SHALL be installed in a neat and workmanlike manner.
- Unused openings: All unused openings in boxes, cabinets, and enclosures must be closed (prevents spread of fire or gases).
- Equipment approval: Equipment shall be acceptable only if listed, labeled, or otherwise found acceptable to the AHJ.
- Working clearances: Adequate space must be maintained around electrical equipment for safety and serviceability.
Article 250 — Grounding & Bonding
Article 250 covers grounding and bonding of all electrical systems. For alarm installers, this is one of the most heavily tested articles.
- Wire type: Grounding wire must be solid copper (NOT stranded, NOT aluminum). All alarm system panels require copper only.
- Wire size: One AWG size smaller (thicker wire) than the largest wire in the panel.
- 14 AWG — panel supplied from 120 VAC with 15-amp overcurrent protection.
- 12 AWG — panel supplied from 120 VAC with 20-amp overcurrent protection.
- Routing: Run the wire DOWN, with large radius curves, the shortest distance possible.
- Priority 1 — Cold water pipe: Connect to the street side of the water meter (use your own clamp).
- Priority 2 — Ground rod: If water pipe is unavailable or plastic.
- Bonding: All grounds must be BONDED together — minimum 6 AWG bonding wire.
Article 300 — Wiring Methods
Article 300 covers how and where conductors are installed, protected, and supported. These physical installation rules apply to all wiring regardless of voltage.
- Physical protection: All wiring must be protected from physical damage.
- Protection within 7 feet of the floor: Cable in areas where it could be damaged must be protected — in conduit, raceway, or otherwise guarded.
- Fastening: Alarm/low-voltage cable must be fastened and supported at least every 18 inches.
- Fittings: All wiring entering boxes or enclosures must pass through approved fittings.
- Wet locations: Boxes and cable in indoor wet locations must have a minimum 1/4-inch airspace between the enclosure and the wall.
- Elevator shafts: Wiring in elevator shafts must directly relate to the elevator — no other circuits allowed.
- Wire markings: NEC rating, UL listing, and NY State Toxicity Requirements must appear on the cable jacket.
- Ducts/plenums (300-22): no wiring in ducts carrying dust or flammable vapor; only Type MI, MC, EMT, IMC, or RMC permitted in air-handling spaces.
- Flexible metal tubing for plenum wiring is also called "Greenfield" or "BX."
Article 500 — Hazardous (Classified) Locations
Article 500 covers wiring in locations where fire or explosion hazards exist. Know the three classes and use approved equipment in these environments.
| Class | Hazard Present | Real-World Examples |
|---|---|---|
| Class I | Flammable gases or vapors | Spray booths, paint facilities, oil/gas processing plants |
| Class II | Combustible dust (explodeable) | Grain elevators, sugar refineries, flour mills, metal powder facilities |
| Class III | Easily ignitable fibers/flyings (not suspended) | Textile mills, woodworking plants, clothing manufacturers |
- Scope (500-1): Covers all voltages where fire/explosion hazards may exist.
- Class I (501-4): Class I hazardous locations (flammable gases/vapors) require explosion-proof equipment and wiring methods per NEC Article 501, Section 501-4.
- Class II (500-14): Switches, relays, and current-breaking contacts for bells, horns, and sirens must have enclosures approved for Class II locations.
- Class III: Alarm systems in Class III locations comply with Article 503 for wiring methods.
- Cable required in hazardous locations: Use PLTC (Power Limited Tray Cable) — standard CL2/CL3 is not acceptable.
Article 725 — Remote Control, Signaling & Power-Limited Circuits
Article 725 defines the three circuit classes governing most alarm system wiring. This is one of the most exam-heavy articles for alarm installers.
Article 725 — Circuit Classes at a Glance
⚠ Class 1 circuits SHALL NOT share a cable with communications circuits (725-5).
- Safety Control (725-4): Remote-control circuits to safety control equipment shall be classified as Class 1 if failure introduces a direct fire or life hazard.
- Class 1 vs. Communications (725-5): Class 1 circuits SHALL NOT be run in the same cable as communications circuits.
- Physical protection (725-18): Where damage to a safety-control Class 1 circuit would create a hazard, conductors must be in conduit, IMC, EMT, Type MI, or Type MC cable.
- Aerial extension (725-19): Class 1 circuits extending aerially beyond one building must also comply with Article 225.
- Over-current protection (725-35): OCDs shall NOT be interchangeable with devices of higher ratings.
- Transformer circuits (725-37): Transformers supplied from light/power circuits must be protected by an OCD rated NOT over 20 amperes.
- Separation (725-38): Class 2 and 3 open conductors must be separated at least 2 inches from Class 1, power, or light conductors.
- Grounding (725-43): Class 2 and 3 circuits must be grounded per Article 250.
- Overcurrent/wiring method (725-12/14): conductors 14 AWG and larger are protected per Article 300; Class 1 wiring method also follows Article 300.
- Smaller conductors (725-15/16): 18/16 AWG permitted for Class 1 circuits within Article 400 ampacity limits, with 600V-rated insulation.
- Class 1 grounding (725-20): Class 1 circuits and equipment must also be grounded per Article 250.
- Power limiting (725-31/32): Class 2/3 power is inherently limited, or limited via source + overcurrent device; power supplies are not paralleled unless listed for that use.
- Marking (725-34): Class 2/3 power supply units must be durably marked, in a visible spot, with their class and electrical rating.
- Co-location: Class 2/3 conductors may share a cable/raceway with jacketed Article 760 or 770 cables.
- Extension beyond one building (725-42): Class 2/3 conductors near conductors over 300V-to-ground must also meet Article 800.
- Class 1 Remote-Control/Signaling (non-power-limited): a separate variant of Class 1, permitted up to 600V with a source that is NOT required to be power-limited — distinct from Class 1 Power-Limited (Class 1 PL), which is capped at 30V/1000VA.
Article 760 — Fire Protection Signaling Circuits
Article 760 specifically governs fire alarm system wiring — from the fire alarm control panel to all connected devices. Covered in full in Module 4.
- NPLFA (Non-Power-Limited Fire Alarm) circuits — require conduit or equivalent protection like Class 1 circuits.
- PLFA (Power-Limited Fire Alarm) circuits — may be run with less stringent protection (like Class 2/3).
- Cable designations: FPL (general purpose), FPLP (plenum), FPLR (riser), FPLS (shielded).
- Circuit integrity: Fire alarm cables must maintain electrical integrity during a fire — survivability is required.
- Fire circuits must be identified as such at the control panel and at every junction, and cannot share a cable/raceway/conduit with high-voltage circuits.
Article 800 — Communications Circuits
Article 800 governs telephone, data, and broadband communications wiring. Alarm systems often use communications infrastructure — covered in depth in Modules 2 and 5.
- Scope: Covers wiring from telephone company terminals to the customer premises equipment.
- Cable types: CM (general), CMR (riser), CMP (plenum), CMX (dwelling only).
- Entrance protection: Communications conductors entering from outside must be protected against lightning and power surges.
- Class 2/3 in same cable: If Class 2/3 circuits share a cable with communications wiring, those circuits become subject to Article 800.
03Part 3 — Basic Electronics & Ohm's Law
The Atom & Electron Flow
All electricity is based on the movement of electrons. Energy applied to a material causes electrons to move from one atom to the next in a chain reaction — this is electric current.
- Conductors (copper, gold, silver) — loosely held outer electrons; current flows freely.
- Insulators (glass, rubber, vinyl, PVC) — tightly held electrons; current cannot flow.
- Electrons move from negative to positive (conventional current shown flowing + to −).
- Like charges repel; unlike charges attract.
Closed vs. Open Circuits
- Closed circuit: current flows — resistance is finite; a complete, unbroken path exists.
- Open circuit: resistance is infinite (∞) — flow stops completely. Any break in the path creates an open.
The Four Electrical Quantities
| Quantity | Unit | Symbol | Notes |
|---|---|---|---|
| Voltage (EMF) | Volts (V) | E | "Pressure" that pushes electrons. EMF = Electromotive Force. |
| Current | Amperes (A) | I | From "Intensity" — electrons passing a point per second. |
| Resistance | Ohms (Ω) | R | Greek letter Omega. Opposition to current flow. |
| Power | Watts (W) or VA | P | Work done in the circuit. AC transformer power is in VA, not Watts. |
Ohm's Law (George Simon Ohm, 1826)
Raise the voltage → current goes up. Raise the resistance → current goes down.
| Formula | Solving for | Use when you know |
|---|---|---|
| E = I × R | Voltage (E) | Current and resistance |
| I = E ÷ R | Current (I) | Voltage and resistance |
| R = E ÷ I | Resistance (R) | Voltage and current |
AWG Wire Resistance Table
| AWG | Ω / 1000 ft @ 70°F | Ω / ft @ 70°F |
|---|---|---|
| 12 | 1.62 | 0.00162 |
| 14 | 2.58 | 0.00258 |
| 16 | 4.10 | 0.00410 |
| 18 | 6.51 | 0.00651 |
| 20 | 10.35 | 0.01035 |
| 22 | 16.43 | 0.01643 |
| 24 | 26.14 | 0.02614 |
Batteries — Series vs. Parallel
| Connection | Voltage Effect | Current (Ah) Effect | Example |
|---|---|---|---|
| Series | Voltages ADD | Same as one battery | 2× 6V @ 7Ah → 12V @ 7Ah |
| Parallel | Same as one battery | Amp-hours ADD | 2× 12V @ 7Ah → 12V @ 14Ah |
Electric Current & the Human Body
| Current | Effect |
|---|---|
| 1 mA | Threshold of sensation — slight tingle |
| 5 mA | Maximum harmless — considered safe |
| 10 – 20 mA | Muscle contractions — cannot let go ("let-go" threshold) |
| 50 – 100 mA | Ventricular fibrillation — can be fatal |
| 100 – 200 mA | Certain death if sustained |
| Over 200 mA | Severe burns — damage to internal organs |
04Part 4 — Series vs. Parallel Circuits
This section is part of the full subscription
Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.
05Part 5 — Wire Types & Cable Ratings
This section is part of the full subscription
Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.
06Part 6 — Resistor Color Codes
This section is part of the full subscription
Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.
07Part 7 — Voltage Drop Calculations
This section is part of the full subscription
Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.
Field notes, common mistakes, exam tips & quick review
This section is part of the full subscription
Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.