Standards, Codes & Basic Electronics

Industry standards, electrical codes, basic electronics and circuit fundamentals, NEC articles in exam order, wire types and fire ratings, grounding rules, resistor color codes, and voltage-drop calculations — the foundation every NYS alarm installer must know cold.

Important acronyms & key terms

ANSI
American National Standards Institute — sets guides for developing standards and codes.
UL
Underwriters Laboratories — tests and lists equipment for specific uses; judges installations against set standards.
NFPA
National Fire Protection Association — sets guidelines used throughout the country.
NFPA 70
The National Electrical Code (NEC).
NFPA 72
Standard for Fire Alarm Systems.
NFPA 101
Life Safety Code.
NFPA 170
Fire Alarm Symbols.
FM
Factory Mutual — tests equipment; not as widely used as NFPA/UL; does not always agree with NFPA.
AHJ
Authority Having Jurisdiction — interprets rules, enforces code, and approves equipment.
MRLS
More Restrictive Local Standard — municipalities may enact stricter standards than the state.
AWG
American Standard Wire Gauge — larger number = smaller wire diameter.
V / E
Volts / Electromotive Force — the force that moves electrons.
I
Intensity / Current — electrons passing a point per second, measured in Amperes.
R / Ω
Resistance — opposition to current flow, measured in Ohms (Ω).
P / VA
Power — work done in an electrical circuit, measured in Watts or Volt-Amperes.
PLFA
Power-Limited Fire Alarm circuit (Article 760) — uses FPL cable.
NPLFA
Non-Power-Limited Fire Alarm circuit (Article 760) — requires conduit like Class 1.
Class 1 PL
Power-Limited Class 1 circuit — source limited to ≤30V and ≤1000VA.
Class 2
Power-limited circuit with lowest energy levels — safest from fire initiation and electric shock standpoints.
Class 3
Like Class 2 but permits higher voltage/current, requiring additional shock-protection safeguards.
Gel Cell Battery
Also called Sealed Lead Acid (SLA) — the standard standby power source used in this industry.
Load
The device that does the work in a circuit. Work can be Heat, Light, Kinetic (movement), or Sound.

Key numbers, codes & rules

NFPA 70
National Electrical Code (NEC)
NFPA 72
Fire Alarm Systems standard
NFPA 101
Life Safety Code
NFPA 170
Fire Alarm Symbols
Art. 90
NEC Purpose
Art. 110
NEC Requirements for Electrical Installations
Art. 250
NEC Grounding & Bonding
Art. 300
NEC Wiring Methods
Art. 500
NEC Hazardous Locations
Art. 725
NEC Remote Control / Signaling / Power-Limited
Art. 760
NEC Fire Protection Signaling Circuits
Art. 800
NEC Communications Circuits
30 V / 1000 VA
Class 1 power-limited circuit max (Art. 725)
2 in
Min. separation: Class 2/3 open conductors from Class 1/power (Art. 725)
20 A
Max OCD for transformer supply circuits (Art. 725)
6 AWG
Minimum bonding wire gauge (Art. 250)
1/4 in
Min. airspace: box/cable from wall in indoor wet locations
7 ft
Height below which cable must be physically protected (Art. 300)
18 in
Max spacing between cable fastenings (Art. 300)
15%
Maximum allowable voltage drop from panel to devices
75 Ω
Coaxial cable impedance for video
RG-59
Coax used for CCTV cameras
RG-6
Coax used for Cable TV
1¼ in / 1/16 in
NEC 300-4: min. bored-hole edge clearance, or steel plate ≥1/16in thick
16.5 VAC / 40 VA
Most common AC transformer rating used in the burglar alarm industry

01Part 1 — Standards & Organizations

Several bodies create the rules that govern alarm installation. Understanding who does what is a guaranteed exam topic.

Standards → Codes → Law → Enforcement

Standards Bodies
• ANSI
• UL
• NFPA
• FM
→
Develop Standards
• NFPA 70 (NEC)
• NFPA 72
• NFPA 101
• NFPA 170
→
Legislated into Law
• State Adoption
• Local Amendments
• MRLS (stricter local)
→
Enforced by AHJ
• Fire Marshal
• Building Inspector
• Electrical Inspector

The Key Organizations

  • ANSI (American National Standards Institute) — writes the guides used to develop standards and codes.
  • UL (Underwriters Laboratories) — tests and lists equipment; judges installations against set standards.
  • UL also lists companies for specific types of installations, in addition to testing/listing equipment and judging installations against set standards.
  • NFPA (National Fire Protection Association) — publishes the national fire and electrical standards (NEC, NFPA 72, 101, 170).
  • FM (Factory Mutual) — also tests equipment but less widely used than NFPA/UL; does not always agree with NFPA.
  • AHJ (Authority Having Jurisdiction) — interprets rules, enforces the code, approves equipment in your local area.
  • MRLS — municipalities have the right to enact a "More Restrictive Local Standard" stricter than the state standard.
  • Code changes happen through committee/board review, or by petition from individuals, industry groups (lobbying), or outside parties.
  • In NY, the DOS Division of Code Enforcement and Administration trains Code Enforcement Officials (CEOs) and maintains the Energy Conservation Construction Code; codes are reviewed on a 3-year ICC cycle (e.g., the 2010 CO-detector requirement).
  • RCNYS: in this "home rule" state, the Residential Code of NYS is an alternate compliance path for residential electrical work.
  • Codes state minimums — a local code cannot override a higher authority (Federal > State > County > Town > AHJ).
Exam Tip
Standards → when written down become Codes → when legislated become Law. The AHJ has the final word on code interpretation at your job site.

NFPA Documents You Must Memorize

DocumentCovers
NFPA 70National Electrical Code (NEC)
NFPA 72Fire Alarm Systems
NFPA 101Life Safety Code
NFPA 170Fire Alarm Symbols
Common mistake
New York City is the ONLY current exception to the NYS Uniform Fire Prevention & Building Code. NYC has its own building and electrical code.

02Part 2 — NEC Articles You Must Know

The National Electrical Code (NEC / NFPA 70) governs all electrical and low-voltage wiring in the United States. First published in 1897, updated every three years, adopted in all 50 states. Know these eight articles in this exact order.

NEC Articles — Exam Order

Art. 90
Purpose of the NEC
Art. 110
Requirements for Electrical Installs
Art. 250
Grounding & Bonding
Art. 300
Wiring Methods
Art. 500
Hazardous Locations
Art. 725
Remote Control / Power-Limited
Art. 760
Fire Protection Signaling
Art. 800
Communications Circuits

Blue = General Electrical · Green = Installation · Red = Safety · Purple/Orange = Alarm-Specific

Article 90 — Purpose of the NEC

Article 90 defines WHY the NEC exists and establishes the authority framework. It is tested on almost every exam.

  • Purpose (90-1): The NEC exists for the practical safeguarding of persons and property from hazards arising from the use of electricity.
  • Adequacy: Contains provisions considered necessary for safety — compliance does NOT guarantee an efficient, convenient, or adequate installation.
  • NOT a design spec: The Code is NOT intended as a design specification and NOT an instruction manual for untrained persons.
  • Enforcement (90-4): Intended for mandatory application by governmental bodies. The AHJ has authority for interpretations, approvals, and granting special permissions.
  • Formal Interpretations (90-5): Formal Interpretation Procedures promote uniformity in applying the NEC.
Exam Tip
Article 90 exam line: "The purpose of the NEC is the practical safeguarding of persons and property." Also: NEC is NOT a design specification or instruction manual for untrained persons.
Field Note
The AHJ on your job site could be a fire marshal, building inspector, or electrical inspector. Whoever has legal jurisdiction — that is your AHJ. Their word is final.

Article 110 — Requirements for Electrical Installations

Article 110 establishes how electrical work must be executed — quality, approval, and workmanship standards.

  • 110-12 Mechanical Execution: All electrical equipment SHALL be installed in a neat and workmanlike manner.
  • Unused openings: All unused openings in boxes, cabinets, and enclosures must be closed (prevents spread of fire or gases).
  • Equipment approval: Equipment shall be acceptable only if listed, labeled, or otherwise found acceptable to the AHJ.
  • Working clearances: Adequate space must be maintained around electrical equipment for safety and serviceability.
Exam Tip
Article 110-12 is the "workmanship" article. The #1 cause of false alarms is bad splices and connections — that is an Article 110-12 violation.
Field Note
Always close unused knockouts in panels and junction boxes. An open hole violates Article 110 and allows rodents, insects, and moisture to enter.

Article 250 — Grounding & Bonding

Article 250 covers grounding and bonding of all electrical systems. For alarm installers, this is one of the most heavily tested articles.

  • Wire type: Grounding wire must be solid copper (NOT stranded, NOT aluminum). All alarm system panels require copper only.
  • Wire size: One AWG size smaller (thicker wire) than the largest wire in the panel.
  • 14 AWG — panel supplied from 120 VAC with 15-amp overcurrent protection.
  • 12 AWG — panel supplied from 120 VAC with 20-amp overcurrent protection.
  • Routing: Run the wire DOWN, with large radius curves, the shortest distance possible.
  • Priority 1 — Cold water pipe: Connect to the street side of the water meter (use your own clamp).
  • Priority 2 — Ground rod: If water pipe is unavailable or plastic.
  • Bonding: All grounds must be BONDED together — minimum 6 AWG bonding wire.
Common mistake
NEVER connect to: hot water pipes, gas pipes, sprinkler pipes, or electrical conduit. These are NOT acceptable ground points.
Exam Tip
Grounding memory rule: SOLID · COPPER · DOWN · LARGE RADIUS · SHORTEST PATH · COLD WATER FIRST · BOND ALL (min. 6 AWG).
Field Note
Always use your own ground clamp — never trust a clamp belonging to another system. You are responsible for your own panel's ground connection.

Article 300 — Wiring Methods

Article 300 covers how and where conductors are installed, protected, and supported. These physical installation rules apply to all wiring regardless of voltage.

  • Physical protection: All wiring must be protected from physical damage.
  • Protection within 7 feet of the floor: Cable in areas where it could be damaged must be protected — in conduit, raceway, or otherwise guarded.
  • Fastening: Alarm/low-voltage cable must be fastened and supported at least every 18 inches.
  • Fittings: All wiring entering boxes or enclosures must pass through approved fittings.
  • Wet locations: Boxes and cable in indoor wet locations must have a minimum 1/4-inch airspace between the enclosure and the wall.
  • Elevator shafts: Wiring in elevator shafts must directly relate to the elevator — no other circuits allowed.
  • Wire markings: NEC rating, UL listing, and NY State Toxicity Requirements must appear on the cable jacket.
  • Ducts/plenums (300-22): no wiring in ducts carrying dust or flammable vapor; only Type MI, MC, EMT, IMC, or RMC permitted in air-handling spaces.
  • Flexible metal tubing for plenum wiring is also called "Greenfield" or "BX."
Exam Tip
Article 300 = the "how to run wire" article. Two most-tested numbers: protect cable within 7 feet of floor, fasten every 18 inches.
Field Note
In NY State, ALL fire alarm cables must also carry NY State Toxicity numbers on the jacket — in addition to NEC and UL markings.

Article 500 — Hazardous (Classified) Locations

Article 500 covers wiring in locations where fire or explosion hazards exist. Know the three classes and use approved equipment in these environments.

ClassHazard PresentReal-World Examples
Class IFlammable gases or vaporsSpray booths, paint facilities, oil/gas processing plants
Class IICombustible dust (explodeable)Grain elevators, sugar refineries, flour mills, metal powder facilities
Class IIIEasily ignitable fibers/flyings (not suspended)Textile mills, woodworking plants, clothing manufacturers
  • Scope (500-1): Covers all voltages where fire/explosion hazards may exist.
  • Class I (501-4): Class I hazardous locations (flammable gases/vapors) require explosion-proof equipment and wiring methods per NEC Article 501, Section 501-4.
  • Class II (500-14): Switches, relays, and current-breaking contacts for bells, horns, and sirens must have enclosures approved for Class II locations.
  • Class III: Alarm systems in Class III locations comply with Article 503 for wiring methods.
  • Cable required in hazardous locations: Use PLTC (Power Limited Tray Cable) — standard CL2/CL3 is not acceptable.
Exam Tip
Memory: Class I = Ignite (gas ignites), Class II = Dust (explosive dust), Class III = Fibers (catch fire). The exam likes Class II examples (grain, flour, sugar).
Field Note
If you are called to install an alarm in a flour mill, grain elevator, or chemical plant — that is a hazardous location. You need equipment rated and listed for that specific class.

Article 725 — Remote Control, Signaling & Power-Limited Circuits

Article 725 defines the three circuit classes governing most alarm system wiring. This is one of the most exam-heavy articles for alarm installers.

Article 725 — Circuit Classes at a Glance

Class 1 (Power-Limited)
Max V: ≤ 30 V
Max VA: ≤ 1000 VA
Full conduit required for safety-control
Class 2
Max V: ≤ 30 V (AC) ≤ 60 V (DC)
Max VA: ≤ 100 VA (AC) ≤ 150 VA (DC)
Lowest energy — minimal protection needed
Class 3
Max V: ≤ 150 V
Max VA: ≤ 100 VA (AC) ≤ 150 VA (DC)
Higher V/I than Class 2; shock safeguards required

⚠ Class 1 circuits SHALL NOT share a cable with communications circuits (725-5).

  • Safety Control (725-4): Remote-control circuits to safety control equipment shall be classified as Class 1 if failure introduces a direct fire or life hazard.
  • Class 1 vs. Communications (725-5): Class 1 circuits SHALL NOT be run in the same cable as communications circuits.
  • Physical protection (725-18): Where damage to a safety-control Class 1 circuit would create a hazard, conductors must be in conduit, IMC, EMT, Type MI, or Type MC cable.
  • Aerial extension (725-19): Class 1 circuits extending aerially beyond one building must also comply with Article 225.
  • Over-current protection (725-35): OCDs shall NOT be interchangeable with devices of higher ratings.
  • Transformer circuits (725-37): Transformers supplied from light/power circuits must be protected by an OCD rated NOT over 20 amperes.
  • Separation (725-38): Class 2 and 3 open conductors must be separated at least 2 inches from Class 1, power, or light conductors.
  • Grounding (725-43): Class 2 and 3 circuits must be grounded per Article 250.
  • Overcurrent/wiring method (725-12/14): conductors 14 AWG and larger are protected per Article 300; Class 1 wiring method also follows Article 300.
  • Smaller conductors (725-15/16): 18/16 AWG permitted for Class 1 circuits within Article 400 ampacity limits, with 600V-rated insulation.
  • Class 1 grounding (725-20): Class 1 circuits and equipment must also be grounded per Article 250.
  • Power limiting (725-31/32): Class 2/3 power is inherently limited, or limited via source + overcurrent device; power supplies are not paralleled unless listed for that use.
  • Marking (725-34): Class 2/3 power supply units must be durably marked, in a visible spot, with their class and electrical rating.
  • Co-location: Class 2/3 conductors may share a cable/raceway with jacketed Article 760 or 770 cables.
  • Extension beyond one building (725-42): Class 2/3 conductors near conductors over 300V-to-ground must also meet Article 800.
  • Class 1 Remote-Control/Signaling (non-power-limited): a separate variant of Class 1, permitted up to 600V with a source that is NOT required to be power-limited — distinct from Class 1 Power-Limited (Class 1 PL), which is capped at 30V/1000VA.
Exam Tip
Two most-tested Art. 725 rules: (1) Class 1 SHALL NOT share a cable with communications circuits. (2) Transformer supply circuit OCD must be ≤ 20 A.
Field Note
In the alarm industry, overcurrent protection almost always means a transformer. The most common burglar alarm transformer is 16.5 VAC, 40 VA (rated in VA, not Watts).

Article 760 — Fire Protection Signaling Circuits

Article 760 specifically governs fire alarm system wiring — from the fire alarm control panel to all connected devices. Covered in full in Module 4.

  • NPLFA (Non-Power-Limited Fire Alarm) circuits — require conduit or equivalent protection like Class 1 circuits.
  • PLFA (Power-Limited Fire Alarm) circuits — may be run with less stringent protection (like Class 2/3).
  • Cable designations: FPL (general purpose), FPLP (plenum), FPLR (riser), FPLS (shielded).
  • Circuit integrity: Fire alarm cables must maintain electrical integrity during a fire — survivability is required.
  • Fire circuits must be identified as such at the control panel and at every junction, and cannot share a cable/raceway/conduit with high-voltage circuits.
Exam Tip
Know the codes: FPL = Fire Power Limited. Add P for plenum, R for riser. Article 760 = fire alarm wiring. Full coverage in Module 4.

Article 800 — Communications Circuits

Article 800 governs telephone, data, and broadband communications wiring. Alarm systems often use communications infrastructure — covered in depth in Modules 2 and 5.

  • Scope: Covers wiring from telephone company terminals to the customer premises equipment.
  • Cable types: CM (general), CMR (riser), CMP (plenum), CMX (dwelling only).
  • Entrance protection: Communications conductors entering from outside must be protected against lightning and power surges.
  • Class 2/3 in same cable: If Class 2/3 circuits share a cable with communications wiring, those circuits become subject to Article 800.
Exam Tip
CM = Communications cable. CMP = Plenum, CMR = Riser, CMX = Dwelling. If Class 2 runs in the same cable as a comm circuit, the whole cable must meet Article 800.

03Part 3 — Basic Electronics & Ohm's Law

The Atom & Electron Flow

All electricity is based on the movement of electrons. Energy applied to a material causes electrons to move from one atom to the next in a chain reaction — this is electric current.

  • Conductors (copper, gold, silver) — loosely held outer electrons; current flows freely.
  • Insulators (glass, rubber, vinyl, PVC) — tightly held electrons; current cannot flow.
  • Electrons move from negative to positive (conventional current shown flowing + to −).
  • Like charges repel; unlike charges attract.

Closed vs. Open Circuits

  • Closed circuit: current flows — resistance is finite; a complete, unbroken path exists.
  • Open circuit: resistance is infinite (∞) — flow stops completely. Any break in the path creates an open.
Exam Tip
Open circuit = ∞ resistance = zero current. This is the basis of EOL (End-Of-Line) resistor supervision — the panel detects a broken wire because current drops to zero.

The Four Electrical Quantities

QuantityUnitSymbolNotes
Voltage (EMF)Volts (V)E"Pressure" that pushes electrons. EMF = Electromotive Force.
CurrentAmperes (A)IFrom "Intensity" — electrons passing a point per second.
ResistanceOhms (Ω)RGreek letter Omega. Opposition to current flow.
PowerWatts (W) or VAPWork done in the circuit. AC transformer power is in VA, not Watts.

Ohm's Law (George Simon Ohm, 1826)

Raise the voltage → current goes up. Raise the resistance → current goes down.

FormulaSolving forUse when you know
E = I × RVoltage (E)Current and resistance
I = E ÷ RCurrent (I)Voltage and resistance
R = E ÷ IResistance (R)Voltage and current
Exam Tip
Ohm's Law memory aid — the E-over-I,R triangle: picture E on top, I and R on the bottom. Cover the value you're solving for and the triangle shows the formula (cover E → I×R, cover I → E÷R, cover R → E÷I).
POWER FORMULA: P = I × E Memory: "P-I-E" — as simple as pie. For AC circuits: Power = Volt-Amperes (VA), not Watts. Example: 16.5 VAC × 2.42 A = 40 VA transformer.

AWG Wire Resistance Table

AWGΩ / 1000 ft @ 70°FΩ / ft @ 70°F
121.620.00162
142.580.00258
164.100.00410
186.510.00651
2010.350.01035
2216.430.01643
2426.140.02614
Common mistake
Resistance increases ~20% from 70°F to 167°F (75°C). In hot environments (attics, boiler rooms), use the higher temperature values to size wire correctly.

Batteries — Series vs. Parallel

ConnectionVoltage EffectCurrent (Ah) EffectExample
SeriesVoltages ADDSame as one battery2× 6V @ 7Ah → 12V @ 7Ah
ParallelSame as one batteryAmp-hours ADD2× 12V @ 7Ah → 12V @ 14Ah
Exam Tip
Series = more VOLTAGE. Parallel = more CAPACITY (amp-hours). Always use same type and same state of charge when connecting batteries.

Electric Current & the Human Body

CurrentEffect
1 mAThreshold of sensation — slight tingle
5 mAMaximum harmless — considered safe
10 – 20 mAMuscle contractions — cannot let go ("let-go" threshold)
50 – 100 mAVentricular fibrillation — can be fatal
100 – 200 mACertain death if sustained
Over 200 mASevere burns — damage to internal organs
Common mistake
It is CURRENT, not voltage, that kills. Even a low voltage can be fatal if body resistance is low (wet hands, open cuts, contact with ground).
Ohm's Law — The Complete Triangle
E = Electromotive Force (Volts) · I = Current (Amps) · R = Resistance (Ohms) · Published by George Simon Ohm, 1826
EElectromotive Force (Volts)ICurrent (Amps)RResistance (Ohms)Cover the letter you want to find — the other two show the formula
Find Voltage (E)
E = I × R
Multiply Current × Resistance
Find Current (I)
I = E ÷ R
Divide Voltage by Resistance
Find Resistance (R)
R = E ÷ I
Divide Voltage by Current
Power Formula — The PIE Triangle
P = Power (Watts / VA) · I = Current (Amps) · E = Voltage (Volts) · Memory hook: as simple as PIE
PPower (Watts / VA)ICurrent (Amps)EVoltage (Volts)Cover the letter you want to find — the other two show the formula · Memory: "PIE"
Find Power (P)
P = I × E
Multiply Current × Voltage
Find Current (I)
I = P ÷ E
Divide Power by Voltage
Find Voltage (E)
E = P ÷ I
Divide Power by Current
Memory hook: "PIE" — P = I × E. For AC transformers, power is rated in VA (Volt-Amperes), not Watts.

04Part 4 — Series vs. Parallel Circuits

This section is part of the full subscription

Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.

05Part 5 — Wire Types & Cable Ratings

This section is part of the full subscription

Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.

06Part 6 — Resistor Color Codes

This section is part of the full subscription

Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.

07Part 7 — Voltage Drop Calculations

This section is part of the full subscription

Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.

Field notes, common mistakes, exam tips & quick review

This section is part of the full subscription

Your free preview includes the opening sections of Module 1 and one 10-question practice attempt. Unlock all study modules, full practice tests, explanations, and repeated practice with a $79 subscription.

Finished studying?

Mark this module complete and head into the practice test. You can come back any time.

All modules